Shuntopac® 20-40 EK

Control unit for heat exchangers with aftercooling etc.

TTM Shuntopac® 20-40 EK is a control and regulation unit for heat exchangers with aftercooling. The Shuntopac 20-40 EK provides quick installation of both control and adjustment valve in a compact unit with thermometers. The unit can be equipped with several components of any brand.

Shuntopac 20-40 EK is supplied with fire and corrosion-proof housing in aluzinc sheet. Standard insulation is AF/Armaflex AF-4. The pipe package consists of fully welded pressure vessel pipes SS 1330-05 and DIN 2391.

EC declaration according to the Machinery Directive 2006/42/EC: “Partly completed machine.”

Equipment

1. Control valve
Seat valve with threaded connection of any make and type. The valve is mounted in a flanged connection to facilitate service and replacement.

2. Measuring socket
Type IMI/TA STAD are fitted on all connections.

3. Drain plug
Version with hose connection R 1/2”.

4. Thermometers
3 pcs, graduated -40 – +40 °C.

5. Shut-off valve
1 pc. low lead ball valve with full flow and high
spindle neck. Mounted in tube pack with conical
coupling.

6. Adjustment valve
1 pc. of any make and size. Mounted on a pipe bundle with conical coupling. IMI/TA STAD is supplied as standard. Can also be supplied with dynamic balancing valve and differential pressure regulator.

TTM Shuntopac® 20-40 EK mounting options

Configuration 09 EK

 

Configuration 10 EK

 

TTM Shuntopac ® 20-40 EK differential pressure measurement

All outside valves on the TTM Shuntopac® 20-40 EK are provided with test sockets, allowing complete differential pressure measurement.

B – A Differential pressure measurement across the adjustment valve.
The flow can be determined with a measuring instrument.

C – A Available differential pressure primary side.

C – H Pressure drop in connected object.

H – B Pressure drop across the control valve.

Dimensions TTM Shuntopac® 20-40 EK

Connection DN20253240
A375375375375
B295295295295
C200200200200
D170170170170
E<175<190<200<205
F85858585
G52525252
H<640<650<660<665
Weight, approx. kg10111213

Max. pressure: 1,0 MPa
Temp. range: -20– +110 °C
Specified dimensions are valid for the standard version. Some variations may occur if alternative equipment is used.

Variable flow on both primary and secondary side. The control valve is mounted in the return pipe.

09 EK

10 EK

Slide
Simonsland in Borås

Wanneer Kanico een nieuwe wijk in Borås ontwikkelt, is TTM verantwoordelijk voor de shuntgroepen in de HVAC-systemen. Het gebied heet Simonsland en omvat 60.000 vierkante meter aan gebouwen.

Slide
Operagebouw Kopenhagen

Het Operahuis van Kopenhagen heeft een oppervlakte van 41.000 vierkante meter, 14 verdiepingen, met 6 podia, een hoofdpodium voor ongeveer 1.500 toeschouwers en 5 podia voor repetities en voorbereidingen.

Slide
Kantoorgebouw in Solna

NCC bouwt zijn nieuwe hoofdkantoor op Järva Krog in Solna. Het nieuwe hoofdkantoor zal strategisch gelegen zijn op een gemakkelijk bereikbare locatie dicht bij de E4-snelweg.